Introduction
Breaker Control Switch is designed on packet type construction. Each packet consists of two electrically independent double break contacts actuated by a Cam. It is developed to cover the wide range of application such as control of Circuit Breaker, Small Motors and wherever severe frequent operations are required.
 
Types

Breaker Control Swicthes are availbale in following types or combination of these types ( Ref. Coding System)

  1. STAY PUT SWITCH
    This type switch is supplied with 30o, 45o, 60oor 90o operating angle

  2. SPRING RETURN SWTICH
    This type switch is supplied for a preferred 45o or 60o

  3. STAY PUT AND SPRING RETURN
    This type switch can have four stay put positions having 45o angle with one spring return position having 45o operating angle. OR
    This type switch can have three stay put positions having 60o angle with one spring return position having 60o operating angle.

  4. SPRING RETURN AND LOST MOTION
    This type of switch is divided in two parts. The front portion of the swtich containing contacts with spring return action and the rear portion accomodating with
    lost motion device. This switch is supplied with 45o or 60o operating angle.

  5. SEQUENCE LOCKING
    n this type of swtich two consecutive movements in clockwise direction are prevented .It is available in 3 position spring return swtich

 
Technical Data
  • ELECTRICAL DATA
    • ContinousCurrent (Ith) 25A / 32A
    • Operational Voltage - 660 Volt
    • HighVoltage Test - 2.5 KV (R.M.S.).
    • Ambient Temperature - 55o
    • Frequencyof Operation - 300 Cycles / Hour
    • Mechanical Life - 1 MillionCycles of Operation
    • Electrical Life - 1 Lac Operation
    • ShortTime Withstand Current - 250 A For 1 Sec.(25 Amp)/300 A For 1 Sec.(32 Amp)
    • Short Time Making &Breaking Capacity - 250 A (25 Amp)/300 A (32 Amp)
DC Breaking Capacity (25Amp)  DC Breaking Capacity (32Amp)
VoltageResistiveInductive
10 M.Sec.
Inductive
20 M.Sec.
Inductive
40 M.Sec.
VoltageResistiveInductive
10 M.Sec.
Inductive
20 M.Sec.
Inductive
40 M.Sec.
5020201565025207.56.5
1032.51.511104431.5
2201.50.50.30.222042.520.5
 
Dimensions